Electrical Requirements

 

Most Cruisair marine air conditioners are available in three different power configurations:

  • 115V 60hz
  • 230V 60hz
  • 220V-240V 50hz

Larger systems are also available with 3-phase compressors. Some 60hz units can run at 50hz, but not all.  Please check the specification sheet or contact your Cruisair dealer if you have a particular power requirement.

The specification sheets will show the running current for the unit. Sometimes both cooling and heating amperages are shown.

To select the circuit breaker for the unit:

  • Multiply the running (heat) amps by 2.5 then chose the next size breaker.
  • If the seawater pump is wired with the unit (not on a pump relay), then add in the pump amps before multiplying by 2.5.

Wire sizing should be done per ABYC requirements. If running on a generator, make sure that it can handle the large starting inrush current of the compressor.

The best solution is to take the spec sheets to the generator supplier and ask for their help.